Abstract
The purpose of this study is to investigate the effect of supply air return from the HVAC system on indoor air quality. We discuss the structure of the formation mechanism in local pollutant concentration distributions using various indices on the ventilation efficiency of a local domain in 3 rooms with different layout of the exhaust outlet location. As a result, when the percentage of the return air at the supply inlet becomes large, visitation frequency of pollutants on a target local domain increases exponentially, and then the averaged concentration of the pollutants of the local domain also increases exponentially.
Translated title of the contribution | FORMATION MECHANISM OF CONTAMINANT CONCENTRATION DISTRIBUTIONS UNDER RE-CIRCULATION OF IN INDOOR AIRFLOW AND HVAC SYSTEM |
---|---|
Original language | Japanese |
Pages (from-to) | 439-447 |
Number of pages | 9 |
Journal | Journal of Environmental Engineering (Japan) |
Volume | 87 |
Issue number | 797 |
DOIs | |
Publication status | Published - 2022 |
All Science Journal Classification (ASJC) codes
- Environmental Engineering