Analysis of an air cycle refrigerator driving air conditioning system integrated desiccant system

S. S. Elsayed, Y. Hamamoto, A. Akisawa, T. Kashiwagi

Research output: Contribution to journalArticlepeer-review

26 Citations (Scopus)

Abstract

This study presents theoretical investigation on the performance of air cycle refrigerator driving air conditioning system integrated desiccant system. Total system performance is evaluated and the system feasibility is examined. The system has such characteristics that (1) safe material of air and water are used as a refrigerant, (2) waste heat from air cycle refrigerator performs the regeneration of desiccant material for energy saving. It has been clarifying that (1) controlling the evaporative cooling process in air washer, the system can operate for a wide range of cooling loads, (2) the total coefficient of performance on air conditioning system is better than the conventional vapor compression system with reheating coil, and (3) the system performance highly depends on the ratio of the amount of outdoor intake air to the supply air.

Original languageEnglish
Pages (from-to)219-228
Number of pages10
JournalInternational Journal of Refrigeration
Volume29
Issue number2
DOIs
Publication statusPublished - Mar 1 2006
Externally publishedYes

All Science Journal Classification (ASJC) codes

  • Building and Construction
  • Mechanical Engineering

Fingerprint Dive into the research topics of 'Analysis of an air cycle refrigerator driving air conditioning system integrated desiccant system'. Together they form a unique fingerprint.