TY - JOUR
T1 - Development of a 3φ-66/6.9 kV-2 MVA REBCO superconducting transformer
AU - Iwakuma, Masataka
AU - Sakaki, Kizen
AU - Tomioka, Akira
AU - Miyayama, Takeji
AU - Konno, Masayuki
AU - Hayashi, Hidemi
AU - Okamoto, Hiroshi
AU - Gosho, Yoshihiro
AU - Eguchi, Tohru
AU - Yoshida, Sigeru
AU - Suzuki, Yoshiaki
AU - Hirai, Hirokazu
AU - Iijima, Yasuhiro
AU - Saitoh, Takashi
AU - Izumi, Teruo
AU - Shiohara, Yuh
N1 - Publisher Copyright:
© 2014 IEEE.
PY - 2015/6/1
Y1 - 2015/6/1
N2 - We have designed and fabricated a 3φ-66 kV/6.9 kV-2 MVA transformer with RE1Ba2Cu3O7-δ(REBCO, RE:Rare Earth, Y, Gd etc.) superconducting tapes. It is a 1/10 model of a 3φ-66 kV/6.9 kV-20 MVA one for a distribution power grid. The superconducting windings were reduced only in current capacity by reducing the number of tapes in parallel conductors. In the primary side, a single REBCO tape with a width of 5 mm was cylindrically wound into 8 layers. In the secondary one, an 8-strand parallel conductor was wound similarly into 2 layers, where each strand was transposed 15 times per one layer. The REBCO tapes for the secondary winding were also scribed by laser into a 3-filament structure to reduce the ac loss. The windings for 3 phases were installed into a GFRP cryostat which had an elliptic-cylinder-shape and three cylindroid bore for an iron core at room-temperature. A Ne turbo-Brayton refrigerator with a cooling capacity of 2 kW at 65 K was developed and located close to the transformer. The windings were cooled with subcooled liquid nitrogen at 65 to 70 K, which was forced-flowed by a pump unit between the transformer and the refrigerator. The completed transformer was first tested in liquid nitrogen at 77 K according to the domestic regulation for conventional transformers. The load loss, i.e., ac loss of the windings, was 26.9 W for the rated operation. The dielectric strength was also verified by applying 350 kV impulse voltage and 140 kV ac voltage for 1 minute.
AB - We have designed and fabricated a 3φ-66 kV/6.9 kV-2 MVA transformer with RE1Ba2Cu3O7-δ(REBCO, RE:Rare Earth, Y, Gd etc.) superconducting tapes. It is a 1/10 model of a 3φ-66 kV/6.9 kV-20 MVA one for a distribution power grid. The superconducting windings were reduced only in current capacity by reducing the number of tapes in parallel conductors. In the primary side, a single REBCO tape with a width of 5 mm was cylindrically wound into 8 layers. In the secondary one, an 8-strand parallel conductor was wound similarly into 2 layers, where each strand was transposed 15 times per one layer. The REBCO tapes for the secondary winding were also scribed by laser into a 3-filament structure to reduce the ac loss. The windings for 3 phases were installed into a GFRP cryostat which had an elliptic-cylinder-shape and three cylindroid bore for an iron core at room-temperature. A Ne turbo-Brayton refrigerator with a cooling capacity of 2 kW at 65 K was developed and located close to the transformer. The windings were cooled with subcooled liquid nitrogen at 65 to 70 K, which was forced-flowed by a pump unit between the transformer and the refrigerator. The completed transformer was first tested in liquid nitrogen at 77 K according to the domestic regulation for conventional transformers. The load loss, i.e., ac loss of the windings, was 26.9 W for the rated operation. The dielectric strength was also verified by applying 350 kV impulse voltage and 140 kV ac voltage for 1 minute.
UR - http://www.scopus.com/inward/record.url?scp=84920895404&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=84920895404&partnerID=8YFLogxK
U2 - 10.1109/TASC.2014.2364615
DO - 10.1109/TASC.2014.2364615
M3 - Article
AN - SCOPUS:84920895404
SN - 1051-8223
VL - 25
JO - IEEE Transactions on Applied Superconductivity
JF - IEEE Transactions on Applied Superconductivity
IS - 3
M1 - 6935085
ER -