Abstract
This study analyzed adverse effects of fusion plants on the stability of small-scale grids through simulation-based case studies. Major frequency fluctuations were observed in the event of a plant start-up and a sudden interruption of fusion electric output power, as represented by plasma disruption, suggesting difficulties in fusion plant installation to majority of countries in the future. To mitigate the adverse effects, a fusion plant combined with an energy storage was proposed and evaluated. The results indicated that large energy storage like pumped-hydro storage could successfully reduce the frequency deviations to the acceptable range. An innovative offshore pumped-hydro storage, marine inverse dam, is also discussed in this paper.
Original language | English |
---|---|
Title of host publication | Fusion Science and Technology |
Publisher | American Nuclear Society |
Pages | 341-345 |
Number of pages | 5 |
Volume | 68 |
Edition | 2 |
ISBN (Electronic) | 9781510811836 |
DOIs | |
Publication status | Published - Sep 1 2015 |
Externally published | Yes |
All Science Journal Classification (ASJC) codes
- Civil and Structural Engineering
- Nuclear and High Energy Physics
- Nuclear Energy and Engineering
- Materials Science(all)
- Mechanical Engineering