Abstract
This study deals with the experiment to clarify the characteristics of adsorption refrigeration system employing activated carbon fiber (ACF) and ethanol pair and to evaluate the performance of adsorber/desorber heat exchanger defined by two kind of index to the system performance. The experiments are carried out by varying system running parameters such as regeneration temperature for adsorber, ethanol temperature in the evaporator, pre-heating/cooling cycle time, adsorption/desorption cycle time. Regeneration temperature for adsorber is from 60 to 90 °C and ethanol temperature is from 0 to 20 °C and pre-heating/cooling cycle time is 60 and 120 second and adsorption/desorption cycle time is from 120 to 300 second. Results show that the system can be operated with regeneration temperature of 60 °C and the system performance improves with increase of ethanol temperature. It is also found that the system performance is affected by regeneration temperature for adsorber and the pre-heating/cooling cycle time and adsorption/desorption cycle time.
Translated title of the contribution | Evaluation of a Fin and Tube Type Adsorber/Desorber Heat Exchanger using =ACF/C<Sub>2</Sub>H<Sub>5</Sub>OH Pair |
---|---|
Original language | Japanese |
Pages (from-to) | 273-282 |
Number of pages | 10 |
Journal | 日本冷凍空調学会論文集 |
Volume | 26 |
Issue number | 3 |
DOIs | |
Publication status | Published - 2009 |