Experiments for actual performance evaluation of room air-conditioners in an experimental house

Research on performance evaluation of room air-conditioners part 1

Daisuke Sumiyoshi, Takashi Ogino, Hisashi Miura, Akinori Hosoi, Takao Sawachi

Research output: Contribution to journalArticle

1 Citation (Scopus)

Abstract

In this research, the experiments to measure the actual performance of room air-conditioners were performed to make appropriate evaluation method of them. Results are as follows: 1. Partial load rates of air-conditioners are very low: especially in the heating use there was a machine whose partial load rates are less than 10 % in 95% of the entire operating hours. 2. COP in actual usage situation was lower than JIS experiment result in most of machines. This tendency was conspicuously appeared in heating. 3. The evaluation approach that can evaluate the actual performance at the heating period and at the low partial load appropriately should be considered.

Original languageEnglish
Pages (from-to)497-505
Number of pages9
JournalJournal of Environmental Engineering (Japan)
Volume78
Issue number688
DOIs
Publication statusPublished - Jun 1 2013

Fingerprint

Heating
Air
Experiments

All Science Journal Classification (ASJC) codes

  • Environmental Engineering

Cite this

Experiments for actual performance evaluation of room air-conditioners in an experimental house : Research on performance evaluation of room air-conditioners part 1. / Sumiyoshi, Daisuke; Ogino, Takashi; Miura, Hisashi; Hosoi, Akinori; Sawachi, Takao.

In: Journal of Environmental Engineering (Japan), Vol. 78, No. 688, 01.06.2013, p. 497-505.

Research output: Contribution to journalArticle

@article{be78c44029674e83b3e3d0ef013ceb32,
title = "Experiments for actual performance evaluation of room air-conditioners in an experimental house: Research on performance evaluation of room air-conditioners part 1",
abstract = "In this research, the experiments to measure the actual performance of room air-conditioners were performed to make appropriate evaluation method of them. Results are as follows: 1. Partial load rates of air-conditioners are very low: especially in the heating use there was a machine whose partial load rates are less than 10 {\%} in 95{\%} of the entire operating hours. 2. COP in actual usage situation was lower than JIS experiment result in most of machines. This tendency was conspicuously appeared in heating. 3. The evaluation approach that can evaluate the actual performance at the heating period and at the low partial load appropriately should be considered.",
author = "Daisuke Sumiyoshi and Takashi Ogino and Hisashi Miura and Akinori Hosoi and Takao Sawachi",
year = "2013",
month = "6",
day = "1",
doi = "10.3130/aije.78.497",
language = "English",
volume = "78",
pages = "497--505",
journal = "Journal of Environmental Engineering (Japan)",
issn = "1348-0685",
publisher = "Architectural Institute of Japan",
number = "688",

}

TY - JOUR

T1 - Experiments for actual performance evaluation of room air-conditioners in an experimental house

T2 - Research on performance evaluation of room air-conditioners part 1

AU - Sumiyoshi, Daisuke

AU - Ogino, Takashi

AU - Miura, Hisashi

AU - Hosoi, Akinori

AU - Sawachi, Takao

PY - 2013/6/1

Y1 - 2013/6/1

N2 - In this research, the experiments to measure the actual performance of room air-conditioners were performed to make appropriate evaluation method of them. Results are as follows: 1. Partial load rates of air-conditioners are very low: especially in the heating use there was a machine whose partial load rates are less than 10 % in 95% of the entire operating hours. 2. COP in actual usage situation was lower than JIS experiment result in most of machines. This tendency was conspicuously appeared in heating. 3. The evaluation approach that can evaluate the actual performance at the heating period and at the low partial load appropriately should be considered.

AB - In this research, the experiments to measure the actual performance of room air-conditioners were performed to make appropriate evaluation method of them. Results are as follows: 1. Partial load rates of air-conditioners are very low: especially in the heating use there was a machine whose partial load rates are less than 10 % in 95% of the entire operating hours. 2. COP in actual usage situation was lower than JIS experiment result in most of machines. This tendency was conspicuously appeared in heating. 3. The evaluation approach that can evaluate the actual performance at the heating period and at the low partial load appropriately should be considered.

UR - http://www.scopus.com/inward/record.url?scp=84884139310&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=84884139310&partnerID=8YFLogxK

U2 - 10.3130/aije.78.497

DO - 10.3130/aije.78.497

M3 - Article

VL - 78

SP - 497

EP - 505

JO - Journal of Environmental Engineering (Japan)

JF - Journal of Environmental Engineering (Japan)

SN - 1348-0685

IS - 688

ER -