ACF/C<Sub>2</Sub>H<Sub>5</Sub>OH系フィンチューブ式吸着器の最適設計に関する解析

Translated title of the contribution: Numerical Analysis on Optimization of a Fin and Tube Type Adsorber/Desorber Heat Exchanger using ACF/C<Sub>2</Sub>H<Sub>5</Sub>OH Pair

仮屋 圭史, 桑原 憲, 小山 繁

    Research output: Contribution to journalArticle

    Abstract

    This study deals with a two dimensional numerical analysis of the fin and tube type adsorber/desorber heat exchanger design such as fin height, fin pitch, fin thickness and tube diameter effect on the performance of closed adsorption cooling system with activated carbon fiber (ACF) of type A-20, which has relatively higher surface area, and ethanol pair. The simulation results show that the fin tube diameter is effective on the performance of the heat exchanger. It is also found that the cycle COP can be optimized in the condition of fin pitch 4.5mm and fin height 20mm, respectively when other parameters are fixed.
    Original languageJapanese
    Pages (from-to)283-294
    Number of pages12
    Journal日本冷凍空調学会論文集
    Volume26
    Issue number3
    DOIs
    Publication statusPublished - 2009

    Fingerprint

    Activated carbon
    Carbon fibers
    Heat exchangers
    Numerical analysis
    Cooling systems
    Ethanol
    Adsorption

    Cite this

    ACF/C<Sub>2</Sub>H<Sub>5</Sub>OH系フィンチューブ式吸着器の最適設計に関する解析. / 仮屋圭史; 桑原憲; 小山繁.

    In: 日本冷凍空調学会論文集, Vol. 26, No. 3, 2009, p. 283-294.

    Research output: Contribution to journalArticle

    @article{3a60dcca67b64fee90e91fcae966a095,
    title = "ACF/C<Sub>2H<Sub>5OH系フィンチューブ式吸着器の最適設計に関する解析",
    abstract = "This study deals with a two dimensional numerical analysis of the fin and tube type adsorber/desorber heat exchanger design such as fin height, fin pitch, fin thickness and tube diameter effect on the performance of closed adsorption cooling system with activated carbon fiber (ACF) of type A-20, which has relatively higher surface area, and ethanol pair. The simulation results show that the fin tube diameter is effective on the performance of the heat exchanger. It is also found that the cycle COP can be optimized in the condition of fin pitch 4.5mm and fin height 20mm, respectively when other parameters are fixed.",
    author = "圭史 仮屋 and 憲 桑原 and 繁 小山",
    year = "2009",
    doi = "10.11322/tjsrae.26.283",
    language = "Japanese",
    volume = "26",
    pages = "283--294",
    journal = "日本冷凍空調学会論文集",
    issn = "1344-4905",
    publisher = "公益社団法人 日本冷凍空調学会",
    number = "3",

    }

    TY - JOUR

    T1 - ACF/C<Sub>2H<Sub>5OH系フィンチューブ式吸着器の最適設計に関する解析

    AU - 仮屋, 圭史

    AU - 桑原, 憲

    AU - 小山, 繁

    PY - 2009

    Y1 - 2009

    N2 - This study deals with a two dimensional numerical analysis of the fin and tube type adsorber/desorber heat exchanger design such as fin height, fin pitch, fin thickness and tube diameter effect on the performance of closed adsorption cooling system with activated carbon fiber (ACF) of type A-20, which has relatively higher surface area, and ethanol pair. The simulation results show that the fin tube diameter is effective on the performance of the heat exchanger. It is also found that the cycle COP can be optimized in the condition of fin pitch 4.5mm and fin height 20mm, respectively when other parameters are fixed.

    AB - This study deals with a two dimensional numerical analysis of the fin and tube type adsorber/desorber heat exchanger design such as fin height, fin pitch, fin thickness and tube diameter effect on the performance of closed adsorption cooling system with activated carbon fiber (ACF) of type A-20, which has relatively higher surface area, and ethanol pair. The simulation results show that the fin tube diameter is effective on the performance of the heat exchanger. It is also found that the cycle COP can be optimized in the condition of fin pitch 4.5mm and fin height 20mm, respectively when other parameters are fixed.

    U2 - 10.11322/tjsrae.26.283

    DO - 10.11322/tjsrae.26.283

    M3 - 記事

    VL - 26

    SP - 283

    EP - 294

    JO - 日本冷凍空調学会論文集

    JF - 日本冷凍空調学会論文集

    SN - 1344-4905

    IS - 3

    ER -