T1 - Returning characteristics of pollutants for a local domain in the presence of returning and recirculating airflow in indoor environments
AU - Lim, Eunsu
AU - Sandberg, Mats
AU - Ito, Kazuhide
N1 - Funding Information:
This study was partially supported by JSPS (Japan Society for the Promotion of Science) Fund for the Promotion of Joint International Research (KAKENHI), Category (A) of Scientific Research (Grant Number JP 18H03807)
Publisher Copyright:
© 2021 The Authors. Indoor Air published by John Wiley & Sons Ltd.
PY - 2021/7
Y1 - 2021/7
N2 - Heating, ventilating, and air-conditioning (HVAC) systems usually supply air, which is a mixture of fresh air from the outdoor environment, and return air from rooms via the ventilation ductwork. This air reduces the heat load and cost impact of air conditioning using outdoor air. This recirculation of room air in air-conditioning systems is reasonable in terms of energy saving; however, the deterioration of air quality might be a concern because of the recirculation of contaminated room air. Here, we numerically investigate the effect of pollutant recirculation/return on the formation of concentration distributions of local pollutants in indoor environments when the mixing ratio of recirculated air in the HVAC system changes. We discuss the detailed structure of the formation mechanism of local pollutant concentration distributions using various indices for indoor ventilation efficiency in simplified room models. Among the indices, visitation frequency and net escape probability are the ones that directly assist in evaluating the recirculation/return characteristics of indoor pollutants. As a result, when the proportion of air that is recirculated becomes large, the number of pollutants returning to a target local domain, the visitation frequency, increases exponentially, and the net escape probability—which directly expresses the probability of pollutant discharged from the target domain—is close to zero.
AB - Heating, ventilating, and air-conditioning (HVAC) systems usually supply air, which is a mixture of fresh air from the outdoor environment, and return air from rooms via the ventilation ductwork. This air reduces the heat load and cost impact of air conditioning using outdoor air. This recirculation of room air in air-conditioning systems is reasonable in terms of energy saving; however, the deterioration of air quality might be a concern because of the recirculation of contaminated room air. Here, we numerically investigate the effect of pollutant recirculation/return on the formation of concentration distributions of local pollutants in indoor environments when the mixing ratio of recirculated air in the HVAC system changes. We discuss the detailed structure of the formation mechanism of local pollutant concentration distributions using various indices for indoor ventilation efficiency in simplified room models. Among the indices, visitation frequency and net escape probability are the ones that directly assist in evaluating the recirculation/return characteristics of indoor pollutants. As a result, when the proportion of air that is recirculated becomes large, the number of pollutants returning to a target local domain, the visitation frequency, increases exponentially, and the net escape probability—which directly expresses the probability of pollutant discharged from the target domain—is close to zero.
UR - http://www.scopus.com/inward/record.url?scp=85100984957&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85100984957&partnerID=8YFLogxK
U2 - 10.1111/ina.12803
DO - 10.1111/ina.12803
M3 - Article
C2 - 33605467
AN - SCOPUS:85100984957
SN - 0905-6947
VL - 31
SP - 1267
EP - 1280
JO - Indoor Air
JF - Indoor Air
IS - 4
ER -