Computer simulation of a silica gel-water adsorption refrigeration cycle - the influence of operating conditions on cooling output and COP

Bidyut B. Saha, Elisa C. Boelman, Takao Kashiwagi

研究成果: ジャーナルへの寄稿Conference article

174 引用 (Scopus)

抜粋

This work deals with the use of adsorption refrigerant cycles driven by waste heat of near ambient temperature. A parametric study was conducted by computer simulation to determine the effects of operating conditions on cooling output and coefficient of performance (COP). A simulation program verified the influence of operating temperatures (hot and cooling water), water flow rates, and adsorption-desorption cycle times. The most influential parameter is the operating temperatures, followed by water flow rates. Cycle time is less influential in quantitative terms but qualitatively is very important.