Control system for the two-arm spectrometer system at RCNP

T. Wakasa, Y. Sakemi, M. Uraki, K. Nagayama, K. Hatanaka

研究成果: Contribution to journalArticle査読

抄録

We have designed and constructed a new control system for the two-arm spectrometers and West-South (WS) beam line at RCNP. The system controls not only the magnets of the spectrometers but also movable devices such as slits. All the instruments are controlled by the system through a local area network. For the dipole magnets of the spectrometers, a high-performance feedback system based on a proportional-integral-differential algorithm was implemented. We have succeeded to change and stabilize the magnetic fields within ±0.05 mT in about 5 min and within about ±0.02 mT after 10 min. The performance of the feedback system satisfies the requirement for the high-resolution experiments with the Grand Raiden spectrometer by using the dispersive beam from the WS beam line.

本文言語英語
ページ(範囲)379-388
ページ数10
ジャーナルNuclear Instruments and Methods in Physics Research, Section A: Accelerators, Spectrometers, Detectors and Associated Equipment
489
1-3
DOI
出版ステータス出版済み - 8 21 2002
外部発表はい

All Science Journal Classification (ASJC) codes

  • Nuclear and High Energy Physics
  • Instrumentation