Desiccant air-conditioning system consisting of heat pump and solar heat collector

Norio Shoda, Hitoshi Kohno, Makoto Koganei, Shizuo Iwamoto, Wanghee Cho, Hideki Yuzawa, Shinsuke Kato

研究成果: 会議への寄与タイプ論文

抜粋

In this study, a desiccant outdoor air-conditioning system that uses high-temperature chilled water (approximately 20 °C) and low-temperature hot water (approximately 55 °C) produced by a high-efficiency heat pump, and hot air produced by solar heat collectors, was proposed. This system treats the total heat load of outdoor air and indoor latent heat load in commercial buildings. In the proposed system, solar heat is effectively used for regeneration of the desiccant in summer and for pre-heating of ventilation air in winter. We have constructed a prototype of this system and evaluated the coefficient of performance (COP) of the entire desiccant air-conditioning system using the measured values of electric energy consumption and treated enthalpy between the outdoor air and supply air.

元の言語英語
出版物ステータス出版済み - 1 1 2015
イベントInternational Conference on Power Engineering, ICOPE 2015 - Yokohama, 日本
継続期間: 11 30 201512 4 2015

その他

その他International Conference on Power Engineering, ICOPE 2015
日本
Yokohama
期間11/30/1512/4/15

All Science Journal Classification (ASJC) codes

  • Energy Engineering and Power Technology

フィンガープリント Desiccant air-conditioning system consisting of heat pump and solar heat collector' の研究トピックを掘り下げます。これらはともに一意のフィンガープリントを構成します。

  • これを引用

    Shoda, N., Kohno, H., Koganei, M., Iwamoto, S., Cho, W., Yuzawa, H., & Kato, S. (2015). Desiccant air-conditioning system consisting of heat pump and solar heat collector. 論文発表場所 International Conference on Power Engineering, ICOPE 2015, Yokohama, 日本.