冷媒R134aの管外凝縮熱伝達率に及ぼすフィン形状の影響

高橋 宏行, 佐伯 主税, 小山 繁

    研究成果: Contribution to journalArticle査読

    抄録

    This paper presents the experimental results on the outside condensation heat tral1sfer coefficient of horizontal enhanced filmed tubes. Three different fin geometry types of three-dimensional enhanced finned tubes were tested. A low-fin-tube (LFT) 19 fin-per-inch (fpi) was also tested for reference. Experimental refrigerant used was R134a. The heat tral1sfer coefficient test was carried out at a condensing temperature of 40°C, at a cooling water velocity of 1.5 m/s, and the heat flux of 10 to 110 kW/m<sup>2</sup>K. The outside condensation heat transfer coefficient of all three dimensional enhanced finned tubes were approximately 1.9 times higher than that of LFTl9fpi at high heat flux range. In low heat flux range, the enhanced finned tube of small circumferential segmentation pitches at the fin tip was shown the highest outside heat transfer coefficient for all tubes tested.
    寄稿の翻訳タイトルEffect of Fin Geometry on Condensation Heat Transfer of Refrigerant R134a on Enhanced Finned Tubes
    本文言語日本語
    ページ(範囲)57-65
    ページ数9
    ジャーナル日本冷凍空調学会論文集
    23
    1
    DOI
    出版ステータス出版済み - 3 31 2006