Entropy generation analysis of an adsorption cooling cycle

Kyaw Thu, Young Deuk Kim, Aung Myat, Won Gee Chun, Kim Choon Ng

研究成果: ジャーナルへの寄稿学術誌査読

31 被引用数 (Scopus)

抄録

This paper discusses the analysis of an adsorption (AD) chiller using system entropy generation as a thermodynamic framework for evaluating total dissipative losses that occurred in a batch-operated AD cycle. The study focuses on an adsorption cycle operating at heat source temperatures ranging from 60 to 85 °C, whilst the chilled water inlet temperature is fixed at 12.5 °C,-a temperature of chilled water deemed useful for dehumidification and cooling. The total entropy generation model examines the processes of key components of the AD chiller such as the heat and mass transfer, flushing and de-superheating of liquid refrigerant. The following key findings are observed: (i) The cycle entropy generation increases with the increase in the heat source temperature (10.8 to 46.2 W/K) and the largest share of entropy generation or rate of energy dissipation occurs at the adsorption process, (ii) the second highest energy rate dissipation is the desorption process, (iii) the remaining energy dissipation rates are the evaporation and condensation processes, respectively. Some of the noteworthy highlights from the study are the inevitable but significant dissipative losses found in switching processes of adsorption-desorption and vice versa, as well as the de-superheating of warm condensate that is refluxed at non-thermal equilibrium conditions from the condenser to the evaporator for the completion of the refrigeration cycle.

本文言語英語
ページ(範囲)143-155
ページ数13
ジャーナルInternational Journal of Heat and Mass Transfer
60
1
DOI
出版ステータス出版済み - 2013
外部発表はい

!!!All Science Journal Classification (ASJC) codes

  • 凝縮系物理学
  • 機械工学
  • 流体および伝熱

フィンガープリント

「Entropy generation analysis of an adsorption cooling cycle」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

引用スタイル