強制対流中におかれた冷却平板上の着霜分布に関する解析

近藤 智恵子, 千秋 隆雄, 小山 繁, 桑原 憲, 小国 研作

    研究成果: Contribution to journalArticle査読

    抄録

    This paper deals the numerical analysis on mass transfer under forced convection cooling. The transients of frost profiles on a cooling plat in a narrow channel were calculated by use of the packaged software with built in some original subroutines. In this paper, the architecture of these subroutines and this benchmark tests were showed. The calculation results exhibit local mass transfer rates and clarified following things. On the leading edge of the cooling plate, the frost accumulation accelerates locally. For the prediction on the cooling plate temperature distribution, to take into account latent heat of sublimation is necessary. In addition, the comparison between calculation and experimental results shows below issues. Both frost distribution profiles overlap in upstream; on the contrary, they do not overlap in the downstream. This comparison result indicates that the super saturation or mist flow is not negligible in the downstream. In terms of total frost weight, both results are roughly agreed and this weight increases proportionally with a run time despite increasing of the heat resistance caused by frost layer.
    寄稿の翻訳タイトルNumerical Study on Frost Profile over the Cooling Plate under Forced Convection
    本文言語日本語
    ページ(範囲)87-95
    ページ数9
    ジャーナル日本冷凍空調学会論文集
    25
    2
    DOI
    出版ステータス出版済み - 2008

    フィンガープリント

    「強制対流中におかれた冷却平板上の着霜分布に関する解析」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

    引用スタイル