Observation of residual surface charge distribution inside an artificial air-filled void due to partial discharge activities at room and liquid nitrogen temperatures

T. Kurihara, J. Suehiro, M. Hara

研究成果: Chapter in Book/Report/Conference proceedingConference contribution

1 被引用数 (Scopus)

抄録

Partial discharge (PD) characteristics within an artificial air-filled void contained in a solid insulator were experimentally investigated under 60 Hz ac voltages at liquid nitrogen temperature (77 K) and room temperature of 298 K. The results show that the first PD inception voltage at 77 K is about twice higher than that at 298 K while successive values at both temperatures are almost the same. The results also show that PD charge magnitude noticeably decreases and PD pulse number remarkably increases with the decrease in the temperature from 298 K to 77 K. The latter results are further discussed based on the observed remarkable decrease in the charged area by a single PD on an inner void surface with the decrease in the temperature.

本文言語英語
ホスト出版物のタイトルProceedings of the 2004 IEEE International Conference on Solid Dielectrics ICSD 2004
ページ308-311
ページ数4
出版ステータス出版済み - 2004
イベントProceedings of the 2004 IEEE International Conference on Solid Dielectrics ICSD 2004 - Toulouse, フランス
継続期間: 7 5 20047 9 2004

出版物シリーズ

名前Proceedings of the 2004 IEEE International Conference on Solid Dielectrics ICSD 2004
1

その他

その他Proceedings of the 2004 IEEE International Conference on Solid Dielectrics ICSD 2004
Countryフランス
CityToulouse
Period7/5/047/9/04