抄録
This paper describes experimental and simulation study results of an air duct system that cools down airflow by using TEMs (thermoelectric modules). This system is designated as TE-AD (thermoelectric air duct) system which consists of twenty four TEMs along with heat sink and fan for circulation of air. Both experimental and simulation results were in good agreement with each other and showed that the TE-AD system reduces room temperature in the range of 1.2-5.3 °C and humidity in the range of 5-31%. The COP (coefficient of performance) of the system ranges from 0.392 to 0.679 under different operating input current for Malaysian weather conditions. By comparing TE-AD system with conventional air conditioning system, energy saving of 38.83% and CO2 emission mitigation of 38.81% was achieved with additional benefits of high reliability and refrigerant free system.
本文言語 | 英語 |
---|---|
ページ(範囲) | 1009-1017 |
ページ数 | 9 |
ジャーナル | Energy |
巻 | 91 |
DOI | |
出版ステータス | 出版済み - 11月 2015 |
!!!All Science Journal Classification (ASJC) codes
- 土木構造工学
- 建築および建設
- 汚染
- 機械工学
- 産業および生産工学
- 電子工学および電気工学