Performance comparison of multi-stage adsorption chillers at the optimal operating conditions

Takahiko Miyazaki, Atsushi Akisawa, Yuki Ueda

研究成果: Contribution to journalArticle査読

抄録

The multi-stage adsorption chillers can be driven by low temperature heat source under 70°C. The purpose of the study is to clarify the maximum specific cooling capacity (SCO of the multistage adsorption chillers by the cycle time optimization. The optimal cycle times of the multi-stage adsorption chillers were found using the particle swarm optimization. The comparison of the optimal performances revealed that the two-stage adsorption chiller was superior to the single-stage and three-stage adsorption chillers within a wide temperature range of the driving heat source.

本文言語英語
ページ(範囲)489-490
ページ数2
ジャーナルNihon Kikai Gakkai Ronbunshu, B Hen/Transactions of the Japan Society of Mechanical Engineers, Part B
76
763
DOI
出版ステータス出版済み - 3 2010
外部発表はい

All Science Journal Classification (ASJC) codes

  • Condensed Matter Physics
  • Mechanical Engineering

フィンガープリント 「Performance comparison of multi-stage adsorption chillers at the optimal operating conditions」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

引用スタイル