Test results of a HTS power transformer connected to a power grid

H. Kimura, K. Honda, H. Hayashi, K. Tsutsumi, Masataka Iwakuma, K. Funaki, T. Bohno, A. Tomioka, Y. Yagi, H. Maruyama, K. Ohashi

研究成果: ジャーナルへの寄稿学術誌査読

11 被引用数 (Scopus)

抄録

A 22 kV/6.9 kV-1 MVA high-Tc superconducting (HTS) power transformer has been developed as a prototype with single-phase part of a 3 MVA HTS power transformer. The prototype unit is cooled by a continuous subcooled liquid nitrogen (LN2) supply system with cryocoolers. During the field tests, the HTS transformer was connected to a distribution line at Imajuku substation (Kyushu Electric Power Co., Inc.) in Fukuoka, and inrush-current test and a long-term operation test were implemented. The test results demonstrated the HTS power transformer's applicability to a power grid.

本文言語英語
ページ(範囲)1694-1697
ページ数4
ジャーナルPhysica C: Superconductivity and its applications
372-376
PART 3
DOI
出版ステータス出版済み - 8月 1 2002

!!!All Science Journal Classification (ASJC) codes

  • 電子材料、光学材料、および磁性材料
  • 凝縮系物理学
  • エネルギー工学および電力技術
  • 電子工学および電気工学

フィンガープリント

「Test results of a HTS power transformer connected to a power grid」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

引用スタイル