The short-circuit test results of 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer

A. Tomioka, T. Otonari, T. Ogata, M. Iwakuma, H. Okamoto, H. Hayashi, Y. Iijima, T. Saito, Y. Gosho, K. Tanabe, T. Izumi, Y. Shiohara

研究成果: ジャーナルへの寄稿学術誌査読

7 被引用数 (Scopus)

抄録

We are developing an elemental technology for 66 kV/6.9 kV 20 MVA-class power transformer with YBCO conductors. The protection of short-circuit technology is one of the elemental technologies for HTS transformer. Since short-circuit current is much higher than critical current of YBCO tape, there is a possibility that superconducting characteristics may be damaged during short-circuit period. We made a conductor to compose the YBCO tape with copper tape. We manufactured 6.9 kV/2.3 kV 400 kVA-class YBCO model transformer using this conductor and performed short-circuit current test. The short-circuit current of primary winding was 346 A which was about six times larger than the rated current. The I-V characteristics of the winding did not change before and after the test. We may consider this conductor withstands short-circuit current.

本文言語英語
ページ(範囲)1374-1378
ページ数5
ジャーナルPhysica C: Superconductivity and its applications
471
21-22
DOI
出版ステータス出版済み - 11月 2011