廃熱利用高温ヒートポンプサイクルの基本性能に関する熱力学的考察

近藤 智恵子, 小山 繁

    研究成果: ジャーナルへの寄稿記事

    抜粋

    To reduce energy consumption utilizing heat recovery systems is increasingly important in industrial applications. The screening of refrigerants is discussed with a case study for high temperature heat pump cycles in this study. The overall coefficients of performance of four different cycle configurations to increase water temperature up to 160 °C using waste heat of 80 °C are thermodynamically compared for several selected refrigerants. This case study suggests that a multiple stage cycle drastically reduces throttling loss in expansion valve and exergy loss in condensers, and consequently achieves the highest overall coefficient of performance (COP) among the cases with a refrigerant having the critical temperature about the target outlet water temperature. Considering many practical benefits, also a cascade cycle that performs relatively high COP can become an expedient solution.
    元の言語Japanese
    ページ(範囲)133-144
    ページ数12
    ジャーナル日本冷凍空調学会論文集
    31
    発行部数2
    DOI
    出版物ステータス出版済み - 2014

      フィンガープリント

    これを引用